Central loose tube cable, outdoor-use, SWA-steel wire armour, HDPE sheath - black, 01x08-fibers G652.D

R855664

Steel wire armoured central loose tube cable with good mechanical protection and thus rodent protected.

The cable features a two jacket construction with up to 24 fibers maximum and is suitable for outdoor duct or direct buried installation.

Technical Data

DESCRIPTION VALUE/VALUE RANGE
Cable type

Central loose tube cable

Jacket material

UV stable HDPE

CPR classification Fca
Armour

Steel wire armoured (SWA)

Cable design

Double jacket

Fiber type

G.652.D

Fiber Count 8
Application

outdoor-use

Cable family code OX1ELWH
DIN/VDE Code A-DQ(ZN)2YB2Y wbg (R 0,63vzk)
DoP no.: D9913
Loose-tube count 1
Fiber count per tube 24
Loose tube nominal diameter [mm] 3.1 mm
Outer jacket nominal thickness [mm] 1.3 mm
Cable outer diameter [mm] 9.9 mm
Cable version

n.a

Standard put-up length on drum 2100 m ± 5%
RoHS

Pass

Mechanical Data

DESCRIPTION VALUE/VALUE RANGE
Cable weight 150.0 kg/km / 101 lbs/1000ft
Tensile performance - in service test method

IEC 60794-1-21:E1

Tensile performance - during installation

4500 N

Tensile Performance during Installation TestMethod

IEC 60794-1-21:E1

Tensile performance - during installation acceptance criteria

Δα ≤ 0,05 dB after test

Crush resistance - long term

2000 N/100mm

Crush resistance - long term test method

IEC 60794-1-21:E3A

Crush resistance - long term acceptance criteria

Δα ≤ 0,05 dB prior release, no damage

Impact resistance

20 Nm, 3 impacts, d=20 mm, R=300 mm

Impact resistance test method

IEC 60794-1-21:E4

Impact resistance acceptance criteria

Δα ≤ 0,05 dB after test, no damage

Torsion

L = 1 m, rotation angle ±180°, 10 cycles

Torsion test method

IEC 60794-1-21:E7

Torsion acceptance criteria

no damage

Cable bend

d=20 x cable diameter, 4 turns, 3 cycles

Cable bend - test method

IEC 60794-1-21:E11A

Cable bend - acceptance criteria

Δα ≤ 0,05 dB after test, no damage

Repeated bending

R=20 x cable diameter, 25 cycles

Repeated bending test method

IEC 60794-1-21:E6

Repeated bending acceptance criteria

no damage

Climatic Data

DESCRIPTION VALUE/VALUE RANGE
Temperature cycling -20 °C +70 °C / -4 °F +158 °F
Temperature cycling - reversible -25 °C +70 °C / -13 °F +158 °F
Installation temperature -5 °C +50 °C / +23 °F +122 °F
Operation temperature -20 °C to +70 °C / -4 °F to +158 °F
Transport / store temperature -25 °C to +70 °C / -13 °F to +158 °F