Central loose tube cable, fire-resistant, universal-use, SWA-steel wire armour, FRLSZH sheath - green, B2ca, 01x04-fibers OM3

R856048

Fire-resistant and steel wire armoured central loose tube cable with good mechanical protection and thus rodent protected.

The cable features a two jacket (both sheath with FRLSZH) construction with up to 24 fibers maximum and is suitable for indoor or outdoor duct or direct buried installation.

Technical Data

DESCRIPTION VALUE/VALUE RANGE
Cable type

Central loose tube cable

CPR classification B2ca
Armour

Steel wire armoured (SWA)

Cable design

Double jacket

Fiber type

OM3

Fiber Count 4
Application

universal-use

Cable family code QX1EFWF FiRis
DIN/VDE Code U-DQ(ZN)HBH wbg (R 0,63vzk) fr
DoP no.: D9007
Loose-tube count 1
Fiber count per tube 24
Loose tube nominal diameter [mm] 3 mm
Outer jacket nominal thickness [mm] 1.3 mm
Cable outer diameter [mm] 10.1 mm
Cable version

Fire-resistant

Standard put-up length on drum 2100 m ± 5%
Halogen free, acid gases

Pass

CPR classification detail B2ca-s1a,d2,a1

Mechanical Data

DESCRIPTION VALUE/VALUE RANGE
Cable weight 185.0 kg/km / 124 lbs/1000ft
Tensile performance - in service

n.a.

Tensile performance - in service test method

IEC 60794-1-21:E1

Tensile performance - in service acceptance criteria

Δα ≤ 0,05 dB

Tensile performance - during installation

6000 N

Tensile Performance during Installation TestMethod

IEC 60794-1-21:E1

Tensile performance - during installation acceptance criteria

Δα ≤ 0,05 dB after test

Crush resistance - long term

2000 N/100mm

Crush resistance - long term test method

IEC 60794-1-21:E3A

Crush resistance - long term acceptance criteria

Δα ≤ 0,05 dB prior release, no damage

Impact resistance

20 Nm, 3 impacts, d=20 mm, R=300 mm

Impact resistance test method

IEC 60794-1-21:E4

Impact resistance acceptance criteria

Δα ≤ 0,05 dB after test, no damage

Torsion

L = 1 m, rotation angle ±180°, 10 cycles

Torsion test method

IEC 60794-1-21:E7

Torsion acceptance criteria

no damage

Cable bend

d=20 x cable diameter, 4 turns, 3 cycles

Cable bend - test method

IEC 60794-1-21:E11A

Cable bend - acceptance criteria

Δα ≤ 0,05 dB after test, no damage

Repeated bending

R=20 x cable diameter, 25 cycles

Repeated bending test method

IEC 60794-1-21:E6

Repeated bending acceptance criteria

no damage

Climatic Data

DESCRIPTION VALUE/VALUE RANGE
Temperature cycling -30 °C +70 °C / -22 °F +158 °F
Temperature cycling - reversible -35 °C +70 °C / -31 °F +158 °F
Installation temperature -5 °C +50 °C / +23 °F +122 °F
Operation temperature -30 °C to +70 °C / -22 °F to +158 °F
Transport / store temperature -35 °C to +70 °C / -31 °F to +158 °F